= hy_gt_vfd(1)


== NAME

hy_gt_vfd - HAL userspace component for Huanyang GT-series VFDs


== SYNOPSIS

*hy_gt_vfd* [_OPTIONS_]


== DESCRIPTION

The hy_gt_vfd component interfaces a Huanyang GT-series VFD to the
LinuxCNC HAL.  The VFD is connected via RS-485 serial to the LinuxCNC
computer.


== Hardware setup

At least some Huanyang GT VFDs must be physically modified to enable
Modbus communication.

The circuit board location marked "SW1" is identified in the manual as
"Switch of terminal resistor for RS485 communication".  On the only
VFD I have experience with, the circuit board contained no switch at
that location, instead holding a pair of crossed jumper wires (top-left
pad connected to bottom-right pad, top-right to bottom-left).  In this
configuration, no Modbus communication is possible.  We had to desolder
the two crossed jumper wires and re-solder them parallel to each other
(top-left to bottom-left, top-right to bottom-right).


== Firmware setup

The Huanyang GT VFD must be configure via the faceplate to talk Modbus
with LinuxCNC.  Consult the Operation section of the Huanyang GT-series
Inverter Manual for details.  Set the following parameters:

P0.01 = 2::

    Set Run Command Source to Modbus serial port.

P0.03::

    Set Maximum Frequency to the maximum frequency you want the VFD to
    output, in Hz.

P0.04::

    Set Upper Frequence Limit to the maximum frequency you want the VFD
    to output, in Hz.  This should be the same as the value in P0.03.

P0.05::

    Set Lower Frequency Limit to the minimum frequency you want the VFD
    to output, in Hz.

P0.07 = 7::

    Set Frequency A Command Source to Modbus serial port.

P2.01 = ???::

    Set Motor Rated Power to the motor's power rating in kW.

P2.02 = ???::

    Set Motor Rated Frequency to the motor's max frequency in Hz.

P2.03 = ???::

    Set Motor Rated Speed to the motor's speed in RPM at its rated
    maximum frequence.

P2.04 = ???::

    Set Motor Rated Voltage to the motor's maximum voltage, in Volts.

P2.05 = ???::

    Set Motor Rated Current to the motor's maximum current, in Amps.

PC.00 = 1::

    Set Local Address to 1.  This matches the default in the hy_gt_vfd
    driver, change this if your setup has special needs.

PC.01 = 5::

    Set Baud Rate Selection to 5 (38400 bps).  This matches the default
    in the hy_gt_vfd driver, change this if your setup has special needs.

        0 = 1200
        1 = 2400
        2 = 4800
        3 = 9600
        4 = 19200
        5 = 38400

PC.02 = 0::

    Set Data Format (8n1 RTU).  This matches the default in the hy_gt_vfd
    driver, change this if your setup has special needs.

PC.03 = 1::

    Set Communication Delay Time to 1 ms.  This is expected by the
    hy_gt_vfd driver.


== OPTIONS

*-b*, *--bits* _N_::

      (default 8) For Modbus communication.  Set number of data bits
      to _N_.  _N_ must be between 5 and 8 inclusive.

*-p*, *--parity* [Even,Odd,None]

      (default None) For Modbus communication.  Set serial parity to Even,
      Odd, or None.

*-r*, *--rate* _N_::

      (default 38400) For Modbus communication.  Set baud rate to _N_.
      It is an error if the rate is not one of the following: 1200,
      2400, 4800, 9600, 19200, 38400

*-s*, *--stopbits* [1,2]::

      (default 1) For Modbus communication.  Set serial stop bits to 1
      or 2.

*-t*, *--target* _N_::

      (default 1) For Modbus communication.  Set Modbus target (slave)
      number.  This must match the device number you set on the Huanyang
      GT VFD.

*-d*, *--device* _PATH_::

      (default /dev/ttyS0) For Modbus communication.  Set the name of
      the serial device node to use.

*-v*, *--verbose*::

      Turn on verbose mode.

*-S*, *--motor-max-speed* _RPM_::

    The motor's max speed in RPM.  This must match the motor speed value
    configured in VFD register P2.03.

*-F*, *--max-frequency* _HZ_::

    This is the maximum output frequency of the VFD in Hz.  It should
    correspond to the motor's rated max frequency, and to the maximum
    and upper limit output frequency configured in VFD register P0.03
    and P0.04.

*-f*, *--min-frequency* _HZ_::

    This is the minimum output frequency of the VFD in Hz.  It should
    correspond to the minimum output frequency configured in VFD
    register P0.05.




== PINS


*hy_gt_vfd.period* (float, in)::

      The period for the driver's update cycle, in seconds. This is
      how frequently the driver will wake up, check its HAL pins, and
      communicate with the VFD.  Must be between 0.001 and 2.000 seconds.
      Default: 0.1 seconds.

*hy_gt_vfd.speed-cmd* (float, in)::

      The requested motor speed, in RPM.

*hy_gt_vfd.speed-fb* (float, out)::

      The motor's current speed, in RPM, reported by the VFD.

*hy_gt_vfd.at-speed* (bit, out)::

      True when the drive is on and at the commanded speed (within 2%),
      False otherwise.

*hy_gt_vfd.freq-cmd* (float, out)::

      The requested output frequency, in Hz.  This is set from the
      .speed-cmd value, and is just shown for debugging purposes.

*hy_gt_vfd.freq-fb* (float, out)::

      The current output frequency of the VFD, in Hz.  This is reported
      from the VFD to the driver.

*hy_gt_vfd.spindle-on* (bit, in)::

      Set this pin True to command the spindle on, at the speed requested
      on the .speed-cmd pin.  Set this pin False to command the spindle
      off.

*hy_gt_vfd.output-voltage* (float, out)::

      The voltage that the VFD is current providing to the motor,
      in Volts.

*hy_gt_vfd.output-current* (float, out)::

      The current that the motor is currently drawing from the VFD,
      in Amperes.

*hy_gt_vfd.output-power* (float, out)::

      The power that the motor is currently drawing from the VFD,
      in Watts.

*hy_gt_vfd.dc-bus-volts* (float, out)::

      The current voltage of the VFD's internal DC power supply, in Volts.

*hy_gt_vfd.modbus-errors* (u32, out)::

      A count of the number of modbus communication errors between the
      driver and the VFD.  The driver is resilient against communication
      errors, but a large or growing number here indicates a problem
      that should be investigated.

*hy_gt_vfd.input-terminal* (float, out)::

        The VFD's input terminal register.

*hy_gt_vfd.output-terminal* (float, out)::

        The VFD's output terminal register.

*hy_gt_vfd.AI1* (float, out)::

        The VFD's AI1 register.

*hy_gt_vfd.AI2* (float, out)::

        The VFD's AI2 register.

*hy_gt_vfd.HDI-frequency* (float, out)::

        The VFD's HDI-frequency register.

*hy_gt_vfd.external-counter* (float, out)::

        The VFD's external counter register.

*hy_gt_vfd.fault-info* (float, out)::

        The VFD's fault info register.




== ISSUES

The VFD produces the output frequency that it sends to the motor by adding
a manually specified offset to the frequency command it gets over modbus.

The manual offset is controlled by pressing the Up/Down arrows on the
faceplate while the VFD is turning the motor.

If you command a speed on the .speed-cmd pin and get a different speed
reported on the .speed-fb pin, first verify that the VFD registers
listed in the FIRMWARE SETUP section above and the driver's command-line
arguments all agree with the info on the motor's name plate.  If you
still aren't getting the speed you expect, zero the VFD's frequency
offset by starting the motor running, then pressing the Up/Down buttons
to zero the offset.